Quick answer. The decision that matters most here is not the rating but whether you also need isolation. VEL-0001 (single-phase) and VEL-0002 and VEL-0003 (three-phase) are variable autotransformers: one winding, with the output taken from a brush running along it, so the output stays electrically connected to the supply whatever the dial reads. Setting a low voltage does not make the downstream circuit safe to touch, and it does not solve the oscilloscope earth problem. Decide on isolation first, then specify the current rating across the whole range, the output range, the enclosure and the protection.
Three variable transformers are listed here, VEL-0001 to VEL-0003: one single-phase and two three-phase, offered in portable, table, floor-mounting, panel-mounting, enclosed and open forms. The names concatenate those options rather than describing one product, so tell the supplier the configuration you want and quote the code. Before any of that, one point matters more than every specification on the page: a variable transformer of this type does not isolate the output from the supply. It is not a substitute for an isolation transformer, and the section below explains why that matters in a student laboratory.
| Code | Phases | Forms offered in the listing |
|---|---|---|
| VEL-0001 | Single phase | Portable, table, floor mounting, enclosed, open |
| VEL-0003 | Three phase | Portable, table, floor mounting, enclosed, open |
| VEL-0002 | Three phase | Flush and back-of-panel mounting, open |
A variable transformer of this kind is an autotransformer: it has one winding, and the output is taken from a brush running along that winding. Because the winding is shared, the output is electrically connected to the incoming supply. Turning the dial to a low voltage reduces the voltage between the output terminals; it does not make either output terminal safe with respect to earth, and the neutral or one line of the supply remains connected through to the output. Two consequences follow, and both are routinely got wrong:
If your laboratory needs both a variable voltage and isolation, ask the supplier whether an isolating variable transformer, that is a variable autotransformer followed by a separate isolation transformer, can be supplied as one unit, and what its rating is. Ask the question explicitly, because catalogues frequently use the words interchangeably.
A variable transformer earns its place in several standard practicals: bringing a machine or transformer up slowly so starting current can be observed; running the open-circuit test on a transformer at reduced voltage; varying the supply to a lamp or heater load to plot a characteristic; checking how a power supply or an appliance behaves at the low and high ends of its input range; and feeding a rectifier or converter experiment at a chosen voltage. For every one of those, size the unit on the current the load actually draws, including its inrush, rather than on the load's steady rating, and ask the supplier to confirm the choice against the load you describe.
The quantity per bench; the weight, since these are heavy for their size and a floor-mounting unit is not moved casually; the supply voltage, frequency and plug type for your country, and the terminal arrangement; whether a test certificate is supplied; spares, in particular brushes and fuses; and the warranty. Note that the three product names in this listing are strings of mounting options rather than product names, so state the phase, rating, mounting and whether you want it enclosed on your enquiry. Any rating quoted is confirmed in writing on the quotation; ask for the test conditions and the temperature rise behind it.
Machines, transformers and the tests these supplies are used for are under Electrical Engineering Trainers and Electrical Training Equipment, with motors under Electric Motors. Converter and drive experiments, where the oscilloscope earth problem is set out at length, are under Power Electronics Trainers. Measurement is under Testing and Measuring Lab Trainers and Power and Instrumentation Lab. Parent range: Training Kits.
Describe the load, including its inrush, and state the phase, mounting and enclosure you need. For example a single-phase enclosed table-mounting unit (VEL-0001) at the current rating your load requires, six benches, with the continuous rating, the output range and the protection fitted confirmed in writing, and state separately whether you also need isolation. Contact Ray Export for prices, ratings and lead times.
No. The units on this page are autotransformers: they have one winding, and the output is taken from a brush running along it. Because the winding is shared, the output is electrically connected to the incoming supply. Turning the dial down reduces the voltage between the output terminals, but it does not make either terminal safe with respect to earth, and the neutral or one line of the supply remains connected through. Treat the output as live at mains potential, whatever the dial reads.
Not on its own. The page is direct: feeding a circuit from a variable transformer and then clipping an earthed probe ground into it is exactly as dangerous as doing so without one. To probe a mains-referenced circuit safely you need a genuine isolation transformer or a differential probe in addition. If you need both a variable voltage and isolation, ask whether an isolating variable transformer, a variable autotransformer followed by a separate isolation transformer, can be supplied as one unit, and at what rating.
The continuous output current, and whether that figure applies at every dial setting; the page calls this the specification most often misread. Ask for the rating in kilovolt-amperes as well, since a transformer rated for a current at full output may not deliver it at a low setting without overheating the winding. Size the unit on the current your load actually draws, including its inrush, rather than its steady rating, describe the load in your enquiry, and have the choice confirmed in writing on the quotation.
It may, so ask. Many variable transformers are wound to give an output above the input at the top of the dial, which the page notes is useful for over-voltage testing and a hazard if nobody expects it. Ask whether the output of the unit you are buying runs from zero to the input voltage or beyond it. For the three-phase units, ask whether the three sections are ganged on one shaft and track together, how closely, and whether the output is three-wire or four-wire with a neutral.
An enclosed unit with shrouded terminals, an earthed case and a cable gland, not an open frame. VEL-0001 and VEL-0003 are offered in portable, table, floor-mounting, enclosed and open forms; VEL-0002 is listed for flush and back-of-panel mounting, open. Ask for the ingress protection rating and whether the dial scale can be read from a standing position. For protection, ask for an input fuse or breaker sized for the transformer, an output fuse, and a voltmeter and ammeter so students see the loading.
The carbon brush is the wearing part. Ask its expected life, whether a technician can change it, and what happens to the output if the brush sticks. Keep brushes and fuses as spares. Ask also whether the rating is continuous or intermittent, whether cooling is natural or forced, and the permitted ambient temperature, which matters in an unconditioned laboratory. These units are heavy for their size, so ask the weight too; a floor-mounting unit is not moved casually.
Ray Export is a manufacturer and exporter of laboratory, scientific and educational equipment based at Plot No. 449, HSIIDC Industrial Area, Saha, Ambala, Haryana 133104, India. Enquiries: [email protected], +91-9817319615.
Written by Palak Mall, Senior Content Writer. Technically reviewed by Arvind Kumar, Lab Equipment Specialist, 12+ years in laboratory and testing instrumentation. Last updated: 17 October 2026.
Specifications for VEL-0001 to VEL-0003, including phase, continuous current and kVA rating, output range, mounting, enclosure, protection, duty and brush arrangements, are confirmed in writing on the quotation. For a test certificate or other certificates, contact us for the latest copies of the relevant certificates. No price is quoted on this page. Listing notes: the three product names are strings of mounting options rather than descriptions of one product, and no current or kVA rating is stated for any code, so state the phase, rating, mounting and enclosure on every enquiry.
Equipment for Education, Engineering and Vocational Training - Variac Single Phase Portable Table / Floor Mounting Enclosed Open for Electrical Training Labs Variac Single Phase Portable Table / Floor Mounting Enclosed Open for Electrical Training Lab
Equipment for Education, Engineering and Vocational Training - Variac Three Phase Flush Back of Panel, Open for Electrical Training Labs Variac Three Phase Flush Back of Panel, Open for Electrical Training Labs
Equipment for Education, Engineering and Vocational Training - Variac Three Phase Portable Table / Floor Mounting Enclosed, Open for Electrical Training Labs Variac Three Phase Portable Table / Floor Mounting Enclosed, Open for Electrical Training Labs